DEVELOPMENT OF AN OPTIMIZED DUAL RELAY SETTING COORDINATION SCHEME FOR DISTRIBUTION NETWORK WITH DISTRIBUTED GENERATION
1 Department of Electrical Engineering, Ahmadu Bello University, Zaria - Nigeria.
2 Department of Electrical Engineering, Ahmadu Bello University, Zaria-Nigeria
3 Ahmadu Bello University, Zaria
* Corresponding author: tundelambo@yahoo.com
2 Department of Electrical Engineering, Ahmadu Bello University, Zaria-Nigeria
3 Ahmadu Bello University, Zaria
* Corresponding author: tundelambo@yahoo.com
Abstract
In Distributed Generation systems (DG), the fault current through a relay in forward
direction is mostly higher than in the reverse direction. Thus, it is desirable to have dual
setting directional over current relay (DOCR) which can operate for both forward and
reverse direction of fault current with two independent relay settings. The presence of DGs
gives additional fault current contribution to the fault location. In this work, the
coordination problem was formulated as a nonlinear optimization problem with the aim of
minimizing the operation times of the relays using bat algorithm. The protection setting
consists of two time-dial settings and one pickup current setting for each relay. The
algorithm was used to obtain the time dial setting (TDS) with the objective of minimizing
the TDS and constraint of satisfying CTI for network topologies and DGs operation. The
performance of the presented coordination strategy was tested on distribution part of IEEE
30 bus system with synchronous DGs. In the case of TDS for without DG penetration for
the relay at maximum/minimum category, the two cases I, II appreciated significantly with
99.96%, and 99.98% respectively. At the maximum/minimum operation for cases I, II with
DG penetration result 99.98% and 99.99% respectively when compared with the base
case. This show that the relay response fast to clear out the fault current in the network.
Also, a reduction in cases I and II of fault current at maximum/minimum level without DG
represent 25.12% and 14.47% respectively. At maximum/minimum fault current for cases
I, II scenario with DG result to 29.33% and 14.94% respectively. The result illustrates that
the algorithm used within dual setting protection scheme is significantly reaching the
optimized coordination and the relay coordination is certain for all simulation scenarios
with remarkable performance.
Keywords
time dial setting. Directional overcurrent relays. Distributed Generation. Bat Algorithm. Rely Coordination.
How to Cite
Lambo, B., Jibril, Y., Jimoh, B., & Abubakar, A. S. (2021). DEVELOPMENT OF AN OPTIMIZED DUAL RELAY SETTING COORDINATION SCHEME FOR DISTRIBUTION NETWORK WITH DISTRIBUTED GENERATION. Zaria Journal of Electrical Engineering Technology, 10(2), 73-83.
B. Lambo, Y. Jibril, B. Jimoh, and A. S. Abubakar, "DEVELOPMENT OF AN OPTIMIZED DUAL RELAY SETTING COORDINATION SCHEME FOR DISTRIBUTION NETWORK WITH DISTRIBUTED GENERATION," Zaria Journal of Electrical Engineering Technology, vol. 10, no. 2, pp. 73-83, September 2021.